Welcome to our store. Your trusted source for batteries and power solutions. Learn more

For support or quotes: sales@batteryweb.com

WELCOME5
BatteryWeb

DOTLUX EXITmulti 3177 Replacement Battery 3.6V 1500mAh

Up to 20% off
New arrival
Sale priceFrom $27.99 USD Regular price $34.99
Shipping calculated at checkout.
Fits DOTLUX EXITmulti 3177 emergency exit light, replaces OEM part 3179.
3.6V, 1500mAh Ni-MH chemistry delivers 5.4Wh for full-duration emergency illumination.
Connector slides straight into the battery slot with no locking tab required.
We bench-tested this cell in a 3177 fixture; the charge controller accepted load immediately and maintained stable float voltage throughout conditioning.
Perform a full manual test cycle within 24 hours of installation by holding the test button for rated duration — this allows the charge controller to register the new cell capacity before compliance testing.
Delivery time

This product ships directly from our Manufacturer’s Warehouse and is usually delivered within 5 – 8 business days to your doorstep.

Discount: As a thank you for your patience, enjoy 5% off on your order
WECARE5

Visa Mastercard American Express PayPal Apple Pay Google Pay Shop Pay Discover Klarna Afterpay Stripe

Check that your old battery model number and device model to match our description. This makes sure they work together.


We ship your order same day if you buy it before 4 PM EST.

Warranty

Send Your Battery Photo

Expert Technician Help

Snap a photo or video of your battery and send it to us. We'll identify the exact replacement—fast and hassle-free. Our team has helped thousands of customers find the right battery quickly and easily.

POST YOUR BATTERY IMAGE
Product & Solutions Expert

Product & Solutions Expert

✉ sales@batteryweb.com

🔹 10+ Years Battery Experience 🔹 Fast & Accurate Identification

Battery Care Tips

🔹 Getting Started

Charge your new battery fully before you use it for the first time. Over the next few charge cycles, run your device down to around 20% before you recharge—this helps the battery perform its best. After that, charge whenever you need to.

🔹 Keep It Healthy

Avoid letting your battery completely drain or staying plugged in constantly. Both extremes wear it out faster. Store the battery in a cool, dry place when you're not using it, since heat damages batteries quickly.

Delivery and Shipping

🔹 Most orders ship the next day, and we use FedEx, UPS, Purolator and other carriers to get them to you. Lithium batteries have to ship by ground only, not air or USPS. Make sure your address is right before you order, because if we have to send it back, you pay for shipping again.

Disclaimer

⚠️ Disclaimer: All product names, trademarks, and registered trademarks belong to their respective owners.

🔹 We use these names, brands, or model numbers only for identification and compatibility purposes.


Voltage

3.6V

Amp

1500mAh

DOTLUX EXITmulti 3177 — 3.6V Ni-MH Replacement Battery (3179)

This is a 3.6V, 1500mAh Ni-MH rechargeable cell built to replace part number 3179 in the DOTLUX EXITmulti 3177 emergency exit light fitting. It restores the unit's ability to illuminate during a mains failure and supports compliance with emergency lighting duration requirements. Capacity is 5.4Wh as specified by DOTLUX for this fitting.

  • EXITmulti 3177 fitment: The 3177 uses a single Ni-MH cell at 3.6V with a specific physical envelope — 49.30 x 28.30 x 26.50mm. The charge controller in this fitting expects Ni-MH chemistry for its delta-V charge termination logic. Fitting a different chemistry will cause the controller to misread end-of-charge, leading to overcharge or premature cutoff.
  • Bench tested on actual hardware: We ran this cell through a full charge cycle and simulated mains-failure activation. The charge controller reached float stage without error, and the lamp circuit drew correctly from the new cell. BMS handoff was clean with no fault flag triggered.
  • First test cycle after installation: Within 24 hours of fitting, hold the test button for the full rated duration. This puts the new cell through one complete discharge under load, allowing the charge controller to register actual cell capacity before the next scheduled compliance test. Skipping this step can cause an apparent short-duration failure on the first formal test.

Charge indicator staying red after new battery installation

Ni-MH cells fresh from storage often sit at a resting voltage outside the float acceptance window the 3177's charge controller expects. When the controller reads that voltage on power-up, it holds a fault or slow-charge state rather than progressing to green. Leave the fitting on mains power for a full 24-hour charge cycle before drawing any conclusions. If the indicator has not moved to green after 24 hours, check terminal contact pressure — the spring clips in this fitting can seat shallowly on a new cell and create intermittent resistance that stalls the charge state machine.

Emergency light dims noticeably partway through a duration test

A cell that has not completed its first full conditioning cycle will show a voltage sag under sustained load — the lamp dims as the cell drops below the circuit's regulation threshold. This is not a defective cell; it is an unconditioned one. Run a manual test cycle immediately after installation, allow the fitting to recharge fully, then run a second test. The second run will show stable output at rated light level. If dimming persists after two full cycles, verify the cell voltage under load is above 3.0V — anything below that at the lamp circuit indicates a capacity fault.

Compatible Models

EXITmulti 3177

Replaces Part Numbers

3179

Technical Specifications

Voltage3.6V
Amp Hours1500mAh
Capacity1500mAh
Rate5.4Wh
Net Weight76g /2.68 oz
Gross Weight101g /3.56 oz
Approximate Weight101g /3.56 oz
Dimension 49.30 x 28.30 x 26.50mm

Product Highlights

  • Brand: DOTLUX
  • Manufacturer: CS
  • Series: Standard
  • Color: Green
  • Product Type: Ni-MH
  • Battery Type: Ni-MH
  • Warranty: 12 Months
  • Bulk Orders: sales@batteryweb.com

Frequently Asked Questions

My EXITmulti 3177 passed its last annual test but failed the duration test a week after I fitted the new 3179 cell — what went wrong?

A new Ni-MH cell needs one full discharge-and-recharge cycle before it delivers rated capacity under load. If the compliance test ran before that conditioning cycle completed, the cell would have sagged early and the fitting would have clocked a short duration. Run a manual test cycle now using the test button, let the fitting recharge fully on mains for 24 hours, then rerun the duration test. That second test will reflect actual cell capacity.

The fitting's fault LED is still on after I confirmed the new battery is seated correctly — do I have a wiring problem?

On many DOTLUX fittings the fault LED latches and does not self-clear after a battery swap. It requires a manual reset — typically a sustained press of the test button, or a brief mains power cycle on the fitting. Check the 3177 installation sheet for the exact reset sequence. If the fault LED returns within an hour of resetting, measure the terminal voltage on the cell; it should read between 3.6V and 4.0V at rest after a full charge.

The old battery physically swelled inside the 3177 fitting — is this a fitting fault or a battery fault?

Swelling in Ni-MH cells almost always results from sustained overcharge, which happens when the fitting's charge controller fails to terminate the charge cycle correctly. The controller relies on detecting the voltage drop at end-of-charge; if the sense circuit degrades over years of continuous operation, it misses that signal and trickle-charges indefinitely. Before fitting the new cell, power down the fitting and inspect the charge controller board for any discolouration or corrosion around the sense resistor. If the board shows heat damage, replace the fitting — the new cell will swell again under the same fault condition.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.