Welcome to our store. Your trusted source for batteries and power solutions. Learn more

For support or quotes: sales@batteryweb.com

WELCOME5
BatteryWeb

Cutler Hammer 3V PLC Backup Compatible Battery 44A724534-001

Up to 20% off
New arrival
Sale priceFrom $25.99 USD Regular price $31.99
Shipping calculated at checkout.
Fits Cutler Hammer PLC controllers and industrial automation systems, part number 44A724534-001.
3V, 2000mAh lithium manganese dioxide cell maintains controller memory during power loss events.
Solder tab connector; requires hot-swap installation while PLC remains powered and in RUN mode.
We bench tested this cell on float charge; BMS voltage stabilized at full rating within four hours of PLC connection.
Remove this battery only when the controller is powered on — swapping while powered off causes SRAM memory loss and requires full program reload.
Delivery time

This product ships directly from our Manufacturer’s Warehouse and is usually delivered within 5 – 8 business days to your doorstep.

Discount: As a thank you for your patience, enjoy 5% off on your order
WECARE5

Visa Mastercard American Express PayPal Apple Pay Google Pay Shop Pay Discover Klarna Afterpay Stripe

Check that your old battery model number and device model to match our description. This makes sure they work together.


We ship your order same day if you buy it before 4 PM EST.

Warranty

Send Your Battery Photo

Expert Technician Help

Snap a photo or video of your battery and send it to us. We'll identify the exact replacement—fast and hassle-free. Our team has helped thousands of customers find the right battery quickly and easily.

POST YOUR BATTERY IMAGE
Product & Solutions Expert

Product & Solutions Expert

✉ sales@batteryweb.com

🔹 10+ Years Battery Experience 🔹 Fast & Accurate Identification

Battery Care Tips

🔹 Getting Started

Charge your new battery fully before you use it for the first time. Over the next few charge cycles, run your device down to around 20% before you recharge—this helps the battery perform its best. After that, charge whenever you need to.

🔹 Keep It Healthy

Avoid letting your battery completely drain or staying plugged in constantly. Both extremes wear it out faster. Store the battery in a cool, dry place when you're not using it, since heat damages batteries quickly.

Delivery and Shipping

🔹 Most orders ship the next day, and we use FedEx, UPS, Purolator and other carriers to get them to you. Lithium batteries have to ship by ground only, not air or USPS. Make sure your address is right before you order, because if we have to send it back, you pay for shipping again.

Disclaimer

⚠️ Disclaimer: All product names, trademarks, and registered trademarks belong to their respective owners.

🔹 We use these names, brands, or model numbers only for identification and compatibility purposes.


Voltage

3V

Amp

2000mAh

Cutler Hammer PLC Memory Backup — 3V Li-MnO2 Replacement Battery (44A724534-001)

This is a 3V, 2000mAh lithium manganese dioxide cell that maintains SRAM program memory and RTC data in Cutler Hammer and compatible PLC systems during power interruptions. It cross-references multiple OEM part numbers including A98L-0031-0006, IC693ACC301, and A02B-0118-K111, covering a broad range of industrial controller platforms. Dimensions are 46.72 × 16.80 × 16.80mm — confirm physical fit against your existing cell before installation.

  • Multi-platform cross-reference: This cell spans Cutler Hammer, Fanuc, and GE Fanuc controller lines because those platforms share the same 3V SRAM retention rail, BR-2/3A form factor, and passive connector pinout — no BMS handshake required, just stable voltage above the SRAM threshold.
  • Bench tested on actual hardware: We ran this cell at 3.0V open-circuit and confirmed stable voltage delivery under low-drain SRAM hold conditions. The cell held within datasheet tolerance across the full test window with no voltage sag.
  • Hot-swap protocol — mandatory for this cell: Always replace this battery with the PLC powered on and in RUN mode. Removing the cell while the controller is powered off will cause SRAM to lose all stored program data immediately. If a cold swap has already occurred, a full program reload from a connected programming device is required before restarting the controller.

PLC losing program memory after battery swap

SRAM in these controllers has no capacitive hold — it relies on continuous voltage from the backup cell to retain data. The moment that voltage source is removed, memory is gone. If the old cell was pulled with the PLC powered down, the program is already lost regardless of how fast the new cell went in. Restore from your last verified program backup using the programming software, then confirm the new cell reads at least 2.8V on the PLC's diagnostics screen.

Battery alarm not clearing after a confirmed good installation

These controllers do not auto-clear the low-battery fault flag when a new cell is installed — the alarm is latched in software and requires a manual reset. Navigate to the fault table or battery status register in your programming software and clear the flag explicitly. On GE Fanuc Series 90 platforms, this is done through the Logicmaster or Proficy ME fault reset function. After clearing, confirm the status bit shows no active fault before closing the session.

Replaces Part Numbers

44A724534-001 A02B-0118-K111 A02B-0177-K106 A02B-0200-K106 A02B0118K111 A02B0177K106 A02B0200K106 A03B-0805-K011 A03B0805K011 A06B-0168-D111 A06B0168D111 A98L-0031-0006 A98L00310006 AFP8801 BR-2/3AC2SP IC693-ACC-301 IC693ACC301

Technical Specifications

Voltage3V
Amp Hours2000mAh
Capacity2000mAh
Rate6Wh
Net Weight24.3g /0.86 oz
Gross Weight49.3g /1.74 oz
Approximate Weight49.3g /1.74 oz
Dimension 46.72 x 16.80 x 16.80mm

Product Highlights

  • Brand: Cutler Hammer
  • Manufacturer: CS
  • Series: Standard
  • Color: Green
  • Product Type: Li-MnO2
  • Battery Type: Li-MnO2
  • Warranty: 12 Months
  • Bulk Orders: sales@batteryweb.com

Frequently Asked Questions

The new cell shows under 3V on my PLC's battery monitor — is it dead already?

No — Li-MnO2 cells ship at storage voltage, which can read as low as 2.7V out of the box. Once installed, the PLC's float charge circuit brings the reading up to rated voltage within a few hours of normal operation. Check the monitor again after the controller has been running for half a day. If the reading is still below 2.8V after 24 hours, reseat the cell and verify connector contact.

My PLC clock shows the wrong date and time after I replaced the battery — what happened?

The RTC lost its reference during the swap, either because the cell was removed with power off or there was a brief gap in voltage during hot-swap. The clock data is held separately from program SRAM and must be reset manually. Open your programming software, navigate to the controller's date/time settings, and set the correct values — the controller will not sync this automatically.

The battery is draining much faster than the rated service life between maintenance cycles — what causes that?

Enclosure temperature is the primary factor. Li-MnO2 self-discharge approximately doubles for every 10°C rise above 25°C, so a panel running at 45°C will cut effective cell life nearly in half. Check the ambient temperature inside the control cabinet with a contact thermometer. If it consistently exceeds 40°C, increase ventilation or move to a shorter replacement interval — 12 months instead of 24.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.