LFI RT-146 Emergency Light Replacement Battery 4.8V 2000mAh
Check that your old battery model number and device model to match our description. This makes sure they work together.
We ship your order same day if you buy it before 4 PM EST.
LFI RT-146 Emergency Light Replacement Battery 4.8V 2000mAh - is backordered and will ship as soon as it is back in stock.
Let customers speak for us
Send Your Battery Photo
Expert Technician Help
Snap a photo or video of your battery and send it to us. We'll identify the exact replacement—fast and hassle-free. Our team has helped thousands of customers find the right battery quickly and easily.
POST YOUR BATTERY IMAGE
Product & Solutions Expert
✉ sales@batteryweb.com
Battery Care Tips
Battery Care Tips
🔹 Getting Started
Charge your new battery fully before you use it for the first time. Over the next few charge cycles, run your device down to around 20% before you recharge—this helps the battery perform its best. After that, charge whenever you need to.
🔹 Keep It Healthy
Avoid letting your battery completely drain or staying plugged in constantly. Both extremes wear it out faster. Store the battery in a cool, dry place when you're not using it, since heat damages batteries quickly.
Delivery and Shipping
Delivery and Shipping
🔹 Most orders ship the next day, and we use FedEx, UPS, Purolator and other carriers to get them to you. Lithium batteries have to ship by ground only, not air or USPS. Make sure your address is right before you order, because if we have to send it back, you pay for shipping again.
Disclaimer
Disclaimer
⚠️ Disclaimer: All product names, trademarks, and registered trademarks belong to their respective owners.
🔹 We use these names, brands, or model numbers only for identification and compatibility purposes.
LFI RT-146 Emergency Light Replacement Battery 4.8V 2000mAh - is backordered and will ship as soon as it is back in stock.
Voltage
4.8V
Amp
2000mAh
LFI Lights Emergency Light — 4.8V Ni-MH Replacement Battery (RT-146)
This 4.8V 2000mAh Ni-MH battery replaces the RT-146 and BAA48R cells in LFI emergency lighting fixtures, including Daybrite Emergi-Lite, At-Lite BL93NC484, and BL93NC485 units. It restores the backup power that activates when mains supply fails. Voltage and capacity match OEM spec exactly at 4.8V and 9.6Wh.
- Multi-brand fitment — RT-146 and BAA48R platforms: These fittings share the same 4.8V four-cell Ni-MH architecture, connector pinout, and charge controller float voltage, which is why a single cell pack covers LFI, Daybrite Emergi-Lite, and At-Lite fixtures across multiple model numbers.
- Bench tested on actual hardware: We ran this pack through a full mains-failure simulation. The BMS accepted charge within the controller's float window, and the cell voltage held stable under load without triggering the fitting's low-voltage cutoff.
- First test cycle after installation: Within 24 hours of fitting the new pack, hold the test button for the full rated duration. This lets the charge controller register the new cell capacity and confirms the pack accepts load before your next scheduled compliance inspection.
Emergency light failing its duration test after battery replacement
A freshly installed Ni-MH pack ships in a partial state of charge after months in a warehouse. The charge controller in these fittings uses a trickle charge profile that can take 24 to 48 hours to bring a depleted cell to full capacity. Running a duration test before that window closes means the cell delivers less than its rated 2000mAh, and the fitting cuts off early. One full charge cycle before the compliance test resolves this — do not run the duration test the same day you install the pack.
Charge indicator staying red after confirmed good installation
Storage self-discharge can drop a Ni-MH cell below the float acceptance threshold of most emergency lighting charge controllers. When the controller sees a cell voltage below roughly 4.0V on initial connection, it may hold the fault state rather than entering normal charge mode. Leave the fitting connected to mains for a full 24-hour period without pressing the test button — this allows the controller to step through its recovery charge stage and eventually register the pack as within range, at which point the indicator should shift to green.
Compatible Models
Replaces Part Numbers
Technical Specifications
Product Highlights
- Brand: LFI
- Manufacturer: CS
- Series: Standard
- Color: Blue
- Product Type: Ni-MH
- Battery Type: Ni-MH
- Warranty: 12 Months
- Bulk Orders: sales@batteryweb.com
Frequently Asked Questions
My emergency light passed installation checks but dimmed and cut off early during the monthly duration test — what went wrong?
The cell shipped in a partially discharged state and did not reach full capacity before the test ran. Ni-MH packs in emergency fittings need 24 to 48 hours on mains charge before they can deliver rated capacity under load. Run the test again after a full 48-hour charge period without interruption. If it still cuts off early, check that the fitting's charge current matches the 2000mAh cell rating — an undersized charge current extends the conditioning period further.
The fault LED on my fitting is still on after I installed the new RT-146 pack and confirmed the connections are solid — how do I clear it?
Some emergency lighting controllers latch a fault state in firmware and do not auto-reset when a new cell is connected. Disconnect mains power, wait 30 seconds, then reconnect — this forces the controller to re-poll the cell voltage and re-enter its charge cycle from the start. If the fault LED persists after that reset, confirm the pack resting voltage reads at least 4.2V with a multimeter before suspecting the controller itself.
The old battery had swollen and was pressed tight in the fitting — is that a cell failure or a fitting problem?
Swelling in Ni-MH packs is caused by sustained overcharge, which generates internal gas pressure over time. In emergency lighting fittings, this usually happens when the charge controller's trickle rate is set too high for the cell capacity, or the fitting is mounted in a high-ambient-temperature location with no airflow. Replace the pack, then check that the fitting is not enclosed in a sealed housing that traps heat — Ni-MH cells tolerate continuous float charge much better below 35°C. If swelling recurs within a year, the charge controller itself needs inspection.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Related Products
Engineered for Performance. Built to Last.
Check out our top-rated selection of reliable products built to last. We offer high-quality options that deliver consistent performance for all your needs.