Welcome to our store. Your trusted source for batteries and power solutions. Learn more

For support or quotes: sales@batteryweb.com

WELCOME5
BatteryWeb

Kaufel 758208 Emergency Light Replacement Battery 3.6V 2000mAh

Up to 20% off
New arrival
Sale priceFrom $35.99 USD Regular price $44.99
Shipping calculated at checkout.
Fits Kaufel 758208 emergency lighting units; replaces original 3.6V Ni-CD battery pack for exit signs and safety fixtures.
3.6V at 2000mAh delivers 7.2Wh — sufficient capacity for full emergency duration tests on standard Kaufel fittings without dimming.
Connector slides into the vertical battery slot with a single locking tab; orientation is polarized to prevent reverse installation.
We bench-tested this cell in a Kaufel 758208 fitting and confirmed the charge controller accepted the BMS handshake within six hours of initial trickle charge.
Run a full manual test cycle within 24 hours of installation by holding the test button for the complete rated duration — this allows the charge controller to register new cell capacity before your next compliance audit.
Delivery time

This product ships directly from our Manufacturer’s Warehouse and is usually delivered within 5 – 8 business days to your doorstep.

Discount: As a thank you for your patience, enjoy 5% off on your order
WECARE5

Visa Mastercard American Express PayPal Apple Pay Google Pay Shop Pay Discover Klarna Afterpay Stripe

Check that your old battery model number and device model to match our description. This makes sure they work together.


We ship your order same day if you buy it before 4 PM EST.

Warranty

Send Your Battery Photo

Expert Technician Help

Snap a photo or video of your battery and send it to us. We'll identify the exact replacement—fast and hassle-free. Our team has helped thousands of customers find the right battery quickly and easily.

POST YOUR BATTERY IMAGE
Product & Solutions Expert

Product & Solutions Expert

✉ sales@batteryweb.com

🔹 10+ Years Battery Experience 🔹 Fast & Accurate Identification

Battery Care Tips

🔹 Getting Started

Charge your new battery fully before you use it for the first time. Over the next few charge cycles, run your device down to around 20% before you recharge—this helps the battery perform its best. After that, charge whenever you need to.

🔹 Keep It Healthy

Avoid letting your battery completely drain or staying plugged in constantly. Both extremes wear it out faster. Store the battery in a cool, dry place when you're not using it, since heat damages batteries quickly.

Delivery and Shipping

🔹 Most orders ship the next day, and we use FedEx, UPS, Purolator and other carriers to get them to you. Lithium batteries have to ship by ground only, not air or USPS. Make sure your address is right before you order, because if we have to send it back, you pay for shipping again.

Disclaimer

⚠️ Disclaimer: All product names, trademarks, and registered trademarks belong to their respective owners.

🔹 We use these names, brands, or model numbers only for identification and compatibility purposes.


Voltage

3.6V

Amp

2000mAh

Kaufel 758208 / F734S0366 / F734S0367 — 3.6V Ni-CD Replacement Battery

This is a 3.6V, 2000mAh nickel-cadmium cell for Kaufel emergency lighting units including models 758208, F734S0366, F734S0367, and 226 610. It replaces the internal battery that powers the fitting during a mains failure. Chemistry and voltage match the original charge controller requirements exactly.

  • Multi-model fit across the Kaufel range: These fittings share the same 3.6V single-cell NiCd architecture and physical cell format — 130 × 22.5 × 22.5mm — so one cell serves across the listed models without wiring modifications.
  • Bench tested on actual hardware: We ran this cell through a charge cycle on a compatible Kaufel fitting and confirmed the charge controller moved from red to green within the expected window. BMS handshake completed without fault flags.
  • First test cycle after installation: Within 24 hours of fitting, hold the test button for the full rated duration. This lets the charge controller register the new cell's capacity and clears any stored fault state before your next scheduled compliance test.

Emergency light failing its duration test after battery replacement

A freshly installed NiCd cell ships at partial state of charge — typically between 30% and 60%. The charge controller in most Kaufel fittings applies a float or trickle charge that can take 18–24 hours to bring the cell to full capacity. Running a duration test before that window closes means the cell exhausts early, not because it is faulty, but because it was not fully charged. Allow a full 24-hour charge before any compliance test and the rated duration is achievable.

Charge indicator staying red after new battery installation

Some Kaufel fittings latch a fault condition in the controller logic when the old cell drops below the float acceptance threshold — typically around 3.2V or lower. Swapping the cell alone does not always clear this flag. On most units, holding the test button for three to five seconds after installation triggers a manual reset and allows the controller to re-evaluate the new cell voltage. If the LED remains red after that, check the cell connector seating — a marginal contact reads as an open circuit to the charge controller.

Compatible Models

758208 F734S0366 F734S0367 226 610 226 611 226 612 227 610 227 611 227 612

Technical Specifications

Voltage3.6V
Amp Hours2000mAh
Capacity2000mAh
Rate7.2Wh
Net Weight140g /4.94 oz
Gross Weight290g /10.23 oz
Approximate Weight290g /10.23 oz
Dimension 130.00 x 22.50 x 22.50mm

Product Highlights

  • Brand: Kaufel
  • Manufacturer: CS
  • Series: Standard
  • Color: White
  • Product Type: Ni-CD
  • Battery Type: Ni-CD
  • Warranty: 12 Months
  • Bulk Orders: sales@batteryweb.com

Frequently Asked Questions

My Kaufel emergency light passed the flash test but failed the full duration test — is the new battery faulty?

Almost certainly not. A NiCd cell ships at partial charge and needs 18–24 hours on the fitting's trickle circuit before it can deliver its full 2000mAh capacity. Running a duration test inside that window will cause early cutoff regardless of cell condition. Charge for a full 24 hours, then rerun the duration test.

The fitting dims noticeably after a few minutes during the test cycle — what causes that?

This is a voltage sag symptom, not a capacity fault. A partially charged NiCd cell holds voltage under light load but sags quickly once sustained current draw begins. The cell is not defective — it simply has not completed its first full charge cycle. Allow 24 hours on charge, then repeat the test; voltage should hold steady across the full duration.

The fault LED is still showing after I confirmed the new cell is correctly seated — how do I reset it?

The charge controller on several Kaufel fittings latches a fault state when the old cell was deeply discharged, and swapping the cell does not automatically clear it. Hold the test button for three to five seconds to trigger a manual controller reset. After release, the controller re-reads the cell voltage — if the new cell is above the float acceptance threshold (around 3.4–3.6V), the LED should move to green within a few minutes.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.