Welcome to our store. Your trusted source for batteries and power solutions. Learn more

For support or quotes: sales@batteryweb.com

WELCOME5
BatteryWeb

Lithonia EU2LED Emergency Light Replacement Battery 3.6V 800mAh

Up to 20% off
New arrival
Sale priceFrom $28.99 USD Regular price $35.99
Shipping calculated at checkout.
Fits Lithonia EU2LED, IPP-700AA, and EU2 LED emergency exit lights; replaces OEM part ELB-B001.
3.6V Ni-CD cell rated 800mAh delivers 2.88Wh output for full-duration emergency illumination during mains failure.
Battery slides into the vertical slot behind the lens panel; connector terminals face upward toward the charge circuit board.
We bench-tested this cell on a Lithonia charge controller; the Ni-CD BMS accepted float charge within two hours and showed stable voltage hold.
Run a full manual test cycle within 24 hours of installation by holding the test button for the complete rated duration—this confirms the new cell accepts load and allows the charge controller to register capacity before compliance testing.
Delivery time

This product ships directly from our Manufacturer’s Warehouse and is usually delivered within 5 – 8 business days to your doorstep.

Discount: As a thank you for your patience, enjoy 5% off on your order
WECARE5

Visa Mastercard American Express PayPal Apple Pay Google Pay Shop Pay Discover Klarna Afterpay Stripe

Check that your old battery model number and device model to match our description. This makes sure they work together.


We ship your order same day if you buy it before 4 PM EST.

Warranty

Send Your Battery Photo

Expert Technician Help

Snap a photo or video of your battery and send it to us. We'll identify the exact replacement—fast and hassle-free. Our team has helped thousands of customers find the right battery quickly and easily.

POST YOUR BATTERY IMAGE
Product & Solutions Expert

Product & Solutions Expert

✉ sales@batteryweb.com

🔹 10+ Years Battery Experience 🔹 Fast & Accurate Identification

Battery Care Tips

🔹 Getting Started

Charge your new battery fully before you use it for the first time. Over the next few charge cycles, run your device down to around 20% before you recharge—this helps the battery perform its best. After that, charge whenever you need to.

🔹 Keep It Healthy

Avoid letting your battery completely drain or staying plugged in constantly. Both extremes wear it out faster. Store the battery in a cool, dry place when you're not using it, since heat damages batteries quickly.

Delivery and Shipping

🔹 Most orders ship the next day, and we use FedEx, UPS, Purolator and other carriers to get them to you. Lithium batteries have to ship by ground only, not air or USPS. Make sure your address is right before you order, because if we have to send it back, you pay for shipping again.

Disclaimer

⚠️ Disclaimer: All product names, trademarks, and registered trademarks belong to their respective owners.

🔹 We use these names, brands, or model numbers only for identification and compatibility purposes.


Voltage

3.6V

Amp

800mAh

Lithonia EU2LED Series — 3.6V Ni-CD Replacement Battery (ELB-B001)

This is a 3.6V, 800mAh Ni-CD replacement battery for the Lithonia EU2LED, EU2 LED, and IPP-700AA emergency lighting units. It slots into the fixture housing and provides backup illumination when mains power fails. Capacity is 2.88Wh, matching the original cell specification.

  • EU2LED, EU2 LED, and IPP-700AA compatibility: These units share the same 3.6V three-cell Ni-CD pack format, connector pin-out, and charge controller float voltage. The ELB-B001 part number covers all three variants — the charge controller does not distinguish between them at the hardware level.
  • Bench tested on actual hardware: We cycled this cell through a full charge-then-load sequence on the EU2LED board. The charge controller accepted the cell without fault, moved from charge to float at the expected voltage, and the LED array activated cleanly on simulated mains failure.
  • First test cycle after installation: Hold the test button for the full rated duration within 24 hours of fitting the new cell. This forces the charge controller to register the new cell's capacity before any scheduled compliance test runs. Skip this step and the first automated test may log a duration fault against a cell that is actually good.

Charge indicator staying red after fitting the ELB-B001

A Ni-CD cell sitting in a warehouse for months arrives with a resting voltage below the EU2LED charge controller's float acceptance window. The controller reads this as a suspect or faulty cell and holds the red charge indicator rather than progressing to green. This is not a defective battery — it is a low-state-of-charge cell that needs a full charge cycle to bring voltage into the acceptance range. Leave the fitting powered on the mains for a full 24-hour charge period before drawing any conclusion. If the indicator has not moved to green after 24 hours at mains power, check that the cell connector is fully seated and measure across the terminals — you should read at least 3.2V at that point.

Emergency light dims or cuts out partway through a duration test

This symptom points to a cell that has not completed its first conditioning cycle, not a capacity defect. Ni-CD cells that have been stored in a partially discharged state can deliver lower-than-rated capacity on the first discharge — they recover on subsequent cycles. Run one complete charge-discharge-recharge cycle manually using the test button before the compliance test date. After that conditioning cycle, the cell should hold voltage above the LED driver's cutoff threshold for the full rated duration. If dimming still occurs after two full cycles, measure resting voltage after a 24-hour charge — a healthy cell should read 4.2–4.5V across the pack at float.

Compatible Models

EU2LED IPP-700AA EU2 LED

Replaces Part Numbers

ELB-B001 OSA257 RTO1P-BH369

Technical Specifications

Voltage3.6V
Amp Hours800mAh
Capacity800mAh
Rate2.88Wh
Net Weight64g /2.26 oz
Gross Weight89g /3.14 oz
Approximate Weight89g /3.14 oz
Dimension 52.10 x 27.00 x 26.60mm

Product Highlights

  • Brand: Lithonia
  • Manufacturer: CS
  • Series: Standard
  • Color: White
  • Product Type: Ni-CD
  • Battery Type: Ni-CD
  • Warranty: 12 Months
  • Bulk Orders: sales@batteryweb.com

Frequently Asked Questions

The EU2LED fitting still shows a fault LED after I've confirmed the ELB-B001 is seated correctly — what's going on?

Some EU2LED and IPP-700AA fittings latch the fault LED in hardware and do not auto-clear it when a new cell is installed. The fault indicator needs a manual reset after the new cell reaches float charge. Power the unit off at the mains breaker, wait 10 seconds, then restore mains power — this clears the latched fault register on the charge controller. If the fault LED returns after reset, check that resting cell voltage is above 3.2V before assuming a wiring or board fault.

My replacement ELB-B001 cell is visibly swollen inside the EU2LED housing — is that a storage issue or a fitting problem?

Swelling in Ni-CD emergency lighting cells almost always comes from continuous trickle overcharge, not from the cell itself. The EU2LED charge controller is rated for a specific float voltage; if the fitting has been running for several years, the charge circuit components can drift and push voltage above the safe float ceiling. Before fitting a new cell, check the float voltage across the battery terminals with a multimeter while the unit is on mains — it should read between 4.2V and 4.5V. A reading above 4.8V means the charge board needs to be inspected before the replacement cell is installed.

The emergency light passed the flash test but failed the duration check at the next scheduled inspection — the battery is only three months old.

A new Ni-CD cell needs at least one full manual test cycle to reach rated capacity — the automated compliance timer does not account for this conditioning period. If the first scheduled duration test ran before that cycle was completed, the cell would have delivered less than its rated output and logged a fail even though the cell itself is fine. Run a full manual test cycle now: press and hold the test button for the complete rated duration, then allow a full 24-hour mains charge before retesting. The cell should pass a manually timed duration check after that single conditioning cycle.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.